– open the UP Application
– add ATV device in DTM Browser (ATV9xx in EIP for instance)
– define a device name and an IP
– in the web pages connected to the drive set this IP as static
– then reboot the drive
– connect the DTM
– make a load data from device to be sure you’ve got the right reference
– configure the following points
– profile as Assembly 100/101
– FDR as enabled stored 10s synchro
– CommandRefParam / Reference source 1 at Embedded Ethernet source
– input phase loss Ignore
– output phase loss ignore
– make a store data to device
– wait the synch is done
– then change the configuration of the FDR from stored to served
– make a store data to device
– rebuild all save and download to the PLC